The control system configuration was designed based on the technical specifications of the induction motor and the turbine unit's sensors. An FC4 frequency controller and a static voltage controller were developed and manufactured for testing. The FC4 frequency controller was tested and its correct operation verified at the Rotava small hydropower plant, equipped with a BÁNKI turbine.
Based on tests at the site with the BÁNKI turbine, a control concept was developed for an induction generator coupled to a pump operating as a turbine in islanded mode.
During islanded operation, two parameters of the generating unit must be controlled: frequency and voltage.
A six-stage SHC-FC4 frequency controller was developed with the ability to adjust the frequency setpoint according to the pressure in the pipeline. The controller uses ballast loads, switching individual load stages at zero crossings, to maintain the generating unit's frequency with high precision.
Voltage control is implemented using a five-stage static capacitor bank and is integrated into the control system software. To prevent the external islanded network from affecting the response and accuracy of the generating unit's voltage regulation, the network was separated from the unit's power output using a rectifier, an industrial DC/DC converter with a 24 V DC output, and a DC/AC inverter.

Control system
A control system based on the UniStream USP-104-x10 PLC was selected for automatic control, with the following functional modules:
- UID-0808 THS (digital input/output module with high-speed inputs)
- UIA-0402 N (analog input/output module)
- UIS-04 PTN (Pt100 temperature measurement module)
User interface
The human-machine interface uses a color touchscreen with a diagonal of 10.4 inches (264 mm) and a resolution of 780×600 pixels. To make the system easy to operate, a set of screens was developed, each covering a particular aspect of the application:
- application overview screen

- generating unit details

- measurement of electrical quantities

- PLC input and output status

- screen for analyzing measurement data

- and a graphical output screen with an XY graph

Data acquisition
Application data is acquired via Ethernet (from a Circutor electrical power analyzer) and through three Snap-In input/output modules:
- UID-0808THS (digital inputs/outputs with high-speed acquisition)
- UIA-0402N (standard module for processing analog inputs and outputs)
- UIS-04PTN (specialized module for connecting temperature sensors)
The program monitors input states and detects any fault conditions. Using a newly developed algorithm, it adjusts the output signal sent to the frequency converter according to the input pressure and water flow through the turbine, with the aim of finding the most efficient operating point. Continuous measurement data is displayed on the screen and simultaneously stored in the PLC's working memory.
Monitored inputs
Binary signals
- Start / Stop switch
- generator overcurrent protection status
- supersynchronous speed monitoring
- voltage and frequency protection status
- main circuit breaker status
- frequency converter operating status (OK / fault)
Analog signals
- pressure in the supply pipe
- negative pressure in the discharge pipe
- water flow through the turbine
- turbine speed
Data received via communications
- phase voltages in phases L1, L2, L3
- line-to-line voltages L1L2, L2L3, L3L1
- currents in phases L1, L2, L3
- active power in phases L1, L2, L3
- reactive power in phases L1, L2, L3
- apparent power in phases L1, L2, L3
- power factor and the Power Factor parameter in phases L1, L2, L3
- total active power
- total reactive power
- total inductive component of reactive power
- total capacitive component of reactive power
- overall power factor and the Power Factor parameter
Generating unit efficiency evaluation
Using these variables, the algorithm determines the generating unit's overall efficiency and displays it on the PLC screen. It first calculates the theoretically available hydraulic power as the product of the water flow through the turbine and the pressure differential, then compares it with the electrical power measured by the power analyzer. Measurements are taken at several frequency settings of the FC4 frequency controller for islanded hydropower plants, and the setting with the highest efficiency is then selected.
This controller can precisely maintain the selected turbine speed through variable electrodynamic braking, switching an air-cooled resistive load connected to the generator on and off.
Automatic operating-point adjustment
In automatic operating-point adjustment mode, the system first determines an approximate controller setting for the current pressure differential. It then fine-tunes the output signal for the SHC-FC4 frequency setpoint according to the generating unit's actual speed. This two-stage adjustment compensates for nonlinearities between the output signal sent to the controller and the actual speed. Only after this precise alignment of the controller's output and input, at thirty-second intervals … up to +15% relative to the tabulated operating point, in 3% steps. Based on the measurements, an XY curve showing efficiency against the percentage output signal to the SHC-FC4 controller is displayed on the PLC screen, and the most suitable value is selected automatically:

If, during operation, the pressure differential changes by more than 10% of its initial value, a new operating point is selected using a new pair of data values from the table.
Voltage control
Speed adjustment is only one of the requirements for the control algorithm. The second requirement is to regulate the system voltage according to the selected speed. Following initial tests, a linear relationship U/f = const was selected, where f is the rotational frequency of the generating unit in Hz (for example, 250 V was set for 30 Hz). Since the islanded system has no external grid available, the generator's operating voltage must be established by progressively switching in a bank of compensation capacitors. The best results (repeatable, stable voltage) were obtained with a capacitor bank whose ratings in kVAr approximately doubled from one stage to the next (e.g. 1, 2, 4, 8, 16). By switching combinations of these stages, any required value from 1 to 63 kVAr could be obtained.



